In a nutshell, the following are the special advantages of our solution of BF Gas Boiler :
Boiler Turn-down without support fuel:
Our design of BFGB is suitable for turn-down ratio of 25% to 110% of MCR without support fuel, instead of 40% to 100% as in conventional design. Hence, better flexibility and fuel savings.
Steam Temperature Control
Our design of BFGB is suitable for steam temperature control range of 30% to 110% of MCR, instead of 50% to 100% as in conventional design. Hence, better flexibility. |
 |
|
|
|
 |
Support Fuel
Our design of BFGB don't require support fuel till the BF gas flow comes below 25% of MCR instead of 40% of MCR, or LHV fall below 450 Kcal/Nm³, as in conventional design. Hence, fuel saving.
Combustion Control / Boiler Trip
In our design of BFGB, the combustion is controlled by sensing the fuel gas temperature (more reliable) compared to Flame Scanner, when temperature of fuel gases fall below 850°C due to BF gas flow below 25% of MCR, or LHV of gas falls below 450 Kcal/Nm³, support fuel cuts-in automatically, to sustain the combustion/heat release, avoid trip and maintain Steam Generation Rate. This arrangement ensures smooth and steady operation, and avoids a trip. |
 |
|
TSPL has many Plants in operation and some of the customers are listed below: |
SISCOL |
- |
SALEM, TAMILNADU, INDIA |
SAW PIPES |
- |
MUNDRA, GUJRAT, INDIA |
VISA STEEL |
- |
JAIPUR, ORISSA, INDIA |
KALYANI |
- |
TADIPATRI, ANDHRA PRADESH, INDIA (Under Execution) |
|